Multi-EV charger load-sharing and panel headroom calculator

Screen shared current, power per active EV, overnight energy per vehicle, and continuous-load headroom for two to eight EVs.

Inputs

Unit system

Results

Overnight energy per EV
33.7 kWh
Power per active EV
4.16 kW
Active ports at once
3 / 3
Electrical load and remaining headroom
Managed EV service load3 of 3 EVs can charge at the same time at the screened site limit.Modeled panel demand (A)Service 200 AExisting 135 AEV load × 1.25 65 AConnected EVs1233 active at once17.3 A per active port
Power per EV when all run
4.16 kW
Overnight range per EV
104.5 mi
Screened continuous EV budget
52 A
Applied total charging current
52 A
Headroom at configured limit
-10 A
Headroom with applied load
0 A
Headroom if all ports use maximum
-85 A

The configured EV limit exceeds the screened headroom. Results apply the lower service budget.

Calculation notes

Subtract the existing non-EV design load from the service rating and divide by 1.25 to screen the new continuous EV charging budget. The applied site limit is also capped by the controller setting and connected port ratings.

If each port can receive at least the assumed 6 A minimum, all vehicles share the current at once. Otherwise, the calculator estimates rotating groups of active ports with equal dwell time over the night.

This is a conservative single-phase planning check. Use a qualified designer for the adopted load calculation, listed energy-management equipment, branch circuits, and phase balancing.

Frequently asked questions

How is panel headroom estimated for a shared EV charger group?

The screening budget is panel rating less non-EV design load, divided by 1.25. The site setting or the sum of the port limits can reduce it further.

Why can some vehicles have zero simultaneous charging power?

When the budget falls below 6 A per connected EV, the model rotates among fewer active ports. Each connected EV receives its share of the total energy over the dwell period.

Can a controller make more home charging capacity available?

A compatible controller can throttle charging as building load changes. Enter the planned ceiling and use the calculated design load for this screening check.