Eight EVs on a load-managed 400 amp depot service

A depot models eight 48 A ports. The existing non-EV design load is 250 A, leaving 150 A of headroom before the continuous-load calculation.

Reduce the site controller setting to leave capacity for another load and check the effect on each EV.

Inputs

Unit system

Results

Overnight energy per EV
25.3 kWh
Power per active EV
3.12 kW
Active ports at once
8 / 8
Electrical load and remaining headroom
Managed EV service load8 of 8 EVs can charge at the same time at the screened site limit.Modeled panel demand (A)Service 400 AExisting 250 AEV load × 1.25 150 AConnected EVs123456788 active at once15 A per active port
Power per EV when all run
3.12 kW
Overnight range per EV
78.3 mi
Screened continuous EV budget
120 A
Applied total charging current
120 A
Headroom at configured limit
-37.5 A
Headroom with applied load
0 A
Headroom if all ports use maximum
-330 A

The configured EV limit exceeds the screened headroom. Results apply the lower service budget.

Calculation notes

Subtract the existing non-EV design load from the service rating and divide by 1.25 to screen the new continuous EV charging budget. The applied site limit is also capped by the controller setting and connected port ratings.

If each port can receive at least the assumed 6 A minimum, all vehicles share the current at once. Otherwise, the calculator estimates rotating groups of active ports with equal dwell time over the night.

This is a conservative single-phase planning check. Use a qualified designer for the adopted load calculation, listed energy-management equipment, branch circuits, and phase balancing.

Frequently asked questions

What is the conservative EV charging cap for the 400 A example?

The available 150 A of design headroom divides by 1.25, giving 120 A of charging current.

How much power does each of the eight depot EVs see simultaneously?

120 A divided equally is 15 A per port. At 208 V, that gives 3.12 kW per port.