Home EV charger breaker and wire sizing calculator

Screen EVSE breaker size with the NEC 125% rule, compare copper and aluminum conductor sizes, and estimate voltage drop.

Inputs

Unit system
The calculation includes the return conductor.

Results

Standard breaker
50 A
Modeled conductor
6 AWG
Estimated voltage drop
1.23%
EVSE circuit and voltage drop
EVSE branch circuitA 50 amp breaker feeds the EVSE over 75 ft of copper. Estimated drop is 1.23%.75 ft one way · copper6 AWG · 50 ABREAKER50 A · 2P125% 50 ATerm 60°C6 AWG (13.3 mm²)75 ft · cap 55 A9.6 kW EVSE circuitEVSE LOAD237.1 V40 A drawSupply 240 VVOLTAGE DROP VS. 3% BUDGET1.23% (2.95 V)Receptacle / GFCI118 W conductor loss
125% minimum
50 A
Ampacity-only minimum
6 AWG
Selected conductor ampacity
55 A
Nominal charging power
9.6 kW
Voltage lost
2.95 V
Conductor power loss
118 W

A 14-50 is an option with a compatible listed EVSE and a properly sized 50 A circuit. NEC 625.54 requires GFCI protection for an EVSE receptacle. Confirm the adopted code and equipment instructions.

Calculation notes

Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.

The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.

Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.

Frequently asked questions

What breaker does a 48 amp home EV charger need in the 125% calculation?

48 A multiplied by 1.25 equals 60 A. Check the EVSE listing, the panel, and the wiring before selecting equipment.

When does a NEMA 14-50 stop being an option for an EVSE?

A 50 A receptacle circuit supports at most 40 A of continuous EV charging under the 125% calculation. Above that, plan for a properly rated hardwired unit.

Why can a long EV charger run need larger wire than ampacity alone suggests?

Resistance rises with conductor length. A larger cross section reduces the voltage lost in both the outgoing and return conductors.