32 amp EVSE wire sizing for a detached garage
A detached garage is 150 ft of conductor from the panel. Compare the ampacity-only copper conductor with the size that meets the 3% design target.
Shorten the route to 75 ft. The voltage drop falls with length at any fixed conductor size.
Results
- Standard breaker
- 40 A
- Modeled conductor
- 6 AWG
- Estimated voltage drop
- 1.97%
- 125% minimum
- 40 A
- Ampacity-only minimum
- 8 AWG
- Selected conductor ampacity
- 55 A
- Nominal charging power
- 7.68 kW
- Voltage lost
- 4.72 V
- Conductor power loss
- 151 W
A 14-50 is an option with a compatible listed EVSE and a properly sized 50 A circuit. NEC 625.54 requires GFCI protection for an EVSE receptacle. Confirm the adopted code and equipment instructions.
Worksheet inputs
- EVSE charging current
- 32 A
- Line-to-line supply
- 240 V residential
- One-way conductor run
- 150 ft
- Conductor
- Copper
- Ampacity column
- 60°C / 140°F
- Voltage drop target
- 3 %
Calculation notes
Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.
The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.
Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.
Frequently asked questions
Why does the detached garage example move from 8 AWG to 6 AWG?
At 150 ft one way, 8 AWG passes the selected ampacity check but misses 3% drop. The next size clears both checks.
Is the trench length the whole length for voltage drop?
Use the actual path from breaker to EVSE as the one-way distance. The worksheet includes the second current-carrying conductor.