16 amp EV charger on a 20 amp circuit

An electrician is screening a small 240 V EVSE for a short attached-garage run. The worksheet uses a 32 ft copper route and the 60°C ampacity column.

Compare the result with a 32 A setting to see how the continuous-load rule changes both breaker and conductor.

Inputs

Unit system
The calculation includes the return conductor.

Results

Standard breaker
20 A
Modeled conductor
12 AWG
Estimated voltage drop
0.84%
EVSE circuit and voltage drop
EVSE branch circuitA 20 amp breaker feeds the EVSE over 32 ft of copper. Estimated drop is 0.84%.32 ft one way · copper12 AWG · 20 ABREAKER20 A · 2P125% 20 ATerm 60°C12 AWG (3.3 mm²)32 ft · cap 20 A3.8 kW EVSE circuitEVSE LOAD238 V16 A drawSupply 240 VVOLTAGE DROP VS. 3% BUDGET0.84% (2.02 V)Receptacle / GFCI32.4 W conductor loss
125% minimum
20 A
Ampacity-only minimum
12 AWG
Selected conductor ampacity
20 A
Nominal charging power
3.84 kW
Voltage lost
2.02 V
Conductor power loss
32.4 W

A 14-50 is an option with a compatible listed EVSE and a properly sized 50 A circuit. NEC 625.54 requires GFCI protection for an EVSE receptacle. Confirm the adopted code and equipment instructions.

Calculation notes

Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.

The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.

Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.

Frequently asked questions

Why does this 16 A charger screen at 20 A?

The continuous-load calculation is 16 × 1.25, which equals 20 A before choosing the standard breaker size.

How much charging power does this 16 A, 240 V setup provide?

The nominal supply is 3.84 kW before line and charging losses.