Voltage drop on a 500 ft EV charger run

A remote parking pad is a 500 ft conductor run from the supply. An electrician is testing a 48 A EVSE and a stricter 2% drop target.

Compare 3% and 2% design targets, then test a lower EVSE current if equipment cost or conduit size is important.

Inputs

Unit system
The calculation includes the return conductor.

Results

Standard breaker
60 A
Modeled conductor
2/0 AWG
Estimated voltage drop
1.94%
EVSE circuit and voltage drop
EVSE branch circuitA 60 amp breaker feeds the EVSE over 500 ft of copper. Estimated drop is 1.94%.500 ft one way · copper2/0 AWG · 60 ABREAKER60 A · 2P125% 60 ATerm 75°C2/0 AWG (67.4 mm²)500 ft · cap 175 A11.5 kW EVSE circuitEVSE LOAD235.3 V48 A drawSupply 240 VVOLTAGE DROP VS. 2% BUDGET1.94% (4.65 V)Hardwired EVSE223.3 W conductor loss
125% minimum
60 A
Ampacity-only minimum
6 AWG
Selected conductor ampacity
175 A
Nominal charging power
11.52 kW
Voltage lost
4.65 V
Conductor power loss
223.3 W

Hardwired EVSE required for this current. A 14-50 receptacle circuit can supply at most 40 A of continuous charging.

Calculation notes

Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.

The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.

Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.

Frequently asked questions

Which requirement drives conductor size on the 500 ft EVSE run?

The 2% voltage drop target drives the size in the example. The minimum conductor from ampacity alone is much smaller.

How does lowering the 48 A setting cut losses on the long driveway?

For a given wire, voltage loss falls in proportion to current. Heat loss in the conductors falls with current squared.