80 amp EVSE on a 100 amp branch circuit
A fleet bay needs to screen an 80 A station at 240 V over a 110 ft copper route. The initial design uses the 75°C column.
Lower the charger setting to 64 A to compare the branch circuit and nominal power.
Results
- Standard breaker
- 100 A
- Modeled conductor
- 3 AWG
- Estimated voltage drop
- 1.8%
- 125% minimum
- 100 A
- Ampacity-only minimum
- 3 AWG
- Selected conductor ampacity
- 100 A
- Nominal charging power
- 19.2 kW
- Voltage lost
- 4.31 V
- Conductor power loss
- 345.2 W
Hardwired EVSE required for this current. A 14-50 receptacle circuit can supply at most 40 A of continuous charging.
Worksheet inputs
- EVSE charging current
- 80 A
- Line-to-line supply
- 240 V residential
- One-way conductor run
- 110 ft
- Conductor
- Copper
- Ampacity column
- 75°C / 167°F
- Voltage drop target
- 3 %
Calculation notes
Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.
The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.
Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.
Frequently asked questions
How much nominal power does the 80 A fleet EVSE draw?
At 240 V and 80 A it draws 19.2 kW before circuit voltage drop.
Why is 100 A assigned to the 80 A charger rather than the whole site?
The 125% calculation sizes the charger branch protection. The site service and panel still need a load calculation for all connected loads.