48 amp hardwired EVSE with a 60 amp breaker

An installer is estimating a 65 ft copper route for a hardwired 48 A station. The wiring method and terminations are assumed to allow a 75°C column check.

Select the 60°C column for the same run to see the effect of a lower ampacity limit.

Inputs

Unit system
The calculation includes the return conductor.

Results

Standard breaker
60 A
Modeled conductor
6 AWG
Estimated voltage drop
1.28%
EVSE circuit and voltage drop
EVSE branch circuitA 60 amp breaker feeds the EVSE over 65 ft of copper. Estimated drop is 1.28%.65 ft one way · copper6 AWG · 60 ABREAKER60 A · 2P125% 60 ATerm 75°C6 AWG (13.3 mm²)65 ft · cap 65 A11.5 kW EVSE circuitEVSE LOAD236.9 V48 A drawSupply 240 VVOLTAGE DROP VS. 3% BUDGET1.28% (3.07 V)Hardwired EVSE147.2 W conductor loss
125% minimum
60 A
Ampacity-only minimum
6 AWG
Selected conductor ampacity
65 A
Nominal charging power
11.52 kW
Voltage lost
3.07 V
Conductor power loss
147.2 W

Hardwired EVSE required for this current. A 14-50 receptacle circuit can supply at most 40 A of continuous charging.

Calculation notes

Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.

The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.

Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.

Frequently asked questions

Why does 6 AWG copper pass this 48 A example in the 75°C column?

Its table ampacity is 65 A in that column, which exceeds the 60 A breaker. Confirm the wiring and termination ratings before applying it.

Does the 48 A configuration fit a NEMA 14-50?

It requires a 60 A circuit in this check. Plan a compatible hardwired EVSE for this charging current.