208 volt EVSE with a long aluminum conductor run

A commercial facility is comparing a 135 ft aluminum route to a 40 A, 208 V EVSE. The estimate assumes the 75°C ampacity column.

Switch the conductor to copper. The size and estimated watts lost will update together.

Inputs

Unit system
The calculation includes the return conductor.

Results

Standard breaker
50 A
Modeled conductor
4 AWG
Estimated voltage drop
2.64%
EVSE circuit and voltage drop
EVSE branch circuitA 50 amp breaker feeds the EVSE over 135 ft of aluminum. Estimated drop is 2.64%.135 ft one way · aluminum4 AWG · 50 ABREAKER50 A · 2P125% 50 ATerm 75°C4 AWG (21.1 mm²)135 ft · cap 65 A8.3 kW EVSE circuitEVSE LOAD202.5 V40 A drawSupply 208 VVOLTAGE DROP VS. 3% BUDGET2.64% (5.49 V)Receptacle / GFCI219.4 W conductor loss
125% minimum
50 A
Ampacity-only minimum
6 AWG
Selected conductor ampacity
65 A
Nominal charging power
8.32 kW
Voltage lost
5.49 V
Conductor power loss
219.4 W

A 14-50 is an option with a compatible listed EVSE and a properly sized 50 A circuit. NEC 625.54 requires GFCI protection for an EVSE receptacle. Confirm the adopted code and equipment instructions.

Calculation notes

Multiply the maximum charging current by 125% and choose the first standard breaker rating at or above that value. The ampacity screen uses the 60°C or 75°C column in NEC Table 310.16, with small-conductor limits. The table assumes 30°C ambient temperature and up to three current-carrying conductors.

The calculator selects a conductor with ampacity at or above the breaker rating, then checks voltage drop for both directions of the run. It uses approximate resistance constants of 12.9 for copper and 21.2 for aluminum in ohm-circular-mil per foot. Power lost is current times voltage drop.

Confirm the circuit design with a qualified electrician and your local authority. Cable type, terminals, temperature, conduit fill, aluminum compatibility, GFCI rules, and the manufacturer listing can change the design.

Frequently asked questions

Why does 208 V make the same lost volts a larger percentage?

Voltage drop percentage divides by supply voltage. A five-volt loss is a larger fraction of 208 V than of 240 V.

Can a 208 V EVSE accept aluminum conductors directly?

Check the product terminal listing. A qualified designer can specify compatible equipment and approved transitions where required.